Your Region:
Call Toll Free: 1 (888) 755-7718 | sales@upsbatterycenter.ca

Peak Energy PK6V8.5F4 6V 8.5 Ah Battery

Peak Energy PK6V8.5F4 6V 8.5 Ah Battery
High Performance
Brand New Fresh Stock
1 Year Warranty Included
Availability: In stock
CAD $27.49

Description

Details

SPECIFICATIONS 
Model DescriptionPeak Energy PK6V8.5F4 rechargeable sealed lead acid (VRLA) battery
Nominal Voltage6 Volt
Capacity (@ 20hr-rate)8.5 Ah
Weight3.72 Lbs (1.69 kg)
Case MaterialA.B.S. (UL94-HB)
TerminalFaston Type 187 (F1) [Position: F4]
Maximum Short Duration Discharge Current127.5 Ah (5 Seconds or Less);
85 Ah (10 Seconds or Less);
48 Ah (60 Seconds or Less)
Internal Resistance10 mOhm (Fully Charged Battery) (Approx)
Energy Density (@ 20hr-rate)1.29 watt-hours/cubic inch (78.75 watt-hours/litre)
Specific Energy (@ 20hr-rate)13.72 watt-hours/pound (30.26 watt-hours/kg)
Operating Temperature RangeDischarge: -4°F (-20°C)  ? 122°F (50°C); 
Recharge: 32°F (0°C)  ? 104°F (40°C); 
Storage:-4°F (-20°C)  ? 104°F (40°C)
Self Discharge RateAbout 3 %/Month @ 68 ? 77°F (20 ? 25°C)


DIMENSIONS

 
Length3.86 in. (98 mm)
Width2.20 in. (56 mm)
Case Height4.65 in. (118 mm)
Terminal Height4.65 in. (118 mm)

    

                              

 CHARTS

 
 
Constant Current Discharge Characteristics at 73.4°F (23°C)

Discharge Time

Discharge Amperes

Capacity in Ah’s

Final Voltage

Discharge

C-Rate

20.0 hr

0.43

8.50

5.25

0.05

9.2 hr

0.85

7.86

5.25

0.10

5.0 hr

1.45

7.20

5.15

0.17

4.1 hr

1.70

6.92

5.10

0.20

2.1 hr

2.98

6.33

4.97

0.35

64.0 min

5.10

5.44

4.77

0.6

32.5 min

8.50

4.60

4.50

1.0

7.2 min

25.5

3.05

3.00

3.0


 

Recharge Method: Connect battery to a Current Limited, Constant Voltage Source.

Limit the initial recharge current to 2.125 Ah or less.

To promote satisfactory performance in Cyclic applications, a minimum recharge current of 850 mA is recommended.

Employ  Charge Voltage Temperature Compensation when battery  temperature is less than 50°F (10°C) 0r greater than 86°F (30°C), Use the Recommended voltage and normalize to 77°F (25°C).

The use of compensation through the whole temperature range is not generally necessary, but doing so may optimize service life.

If the Recommended recharge voltage is used, no Temperature Compensation is required within the range of 50 ? 86°F (10 ? 30°C)

Cyclic Application Recharge Voltage (77°F / 25°C)

Minimum

Recommended

Maximum

 


Volts D.C.

Per Cell

7.20

7.28

7.35

2.40

2.425

2.45

Temperature Coefficient: -2.8mV/°F/Cell (-5mV/°C/Cell)

Standby Application Recharge Voltage (77°F/25°C)

Minimum

Recommended

Maximum

 


Volts D.C.

Per Cell

6.25

6.83

6.90

2.25

2.275

2.30

Temperature Coefficient: -1.7mV/°F/Cell (-3mV/°C/Cell)