Peak Energy PK12V40 12V 40Ah Battery

Peak Energy PK12V40 12V 40Ah Battery
High Performance
Brand New Fresh Stock
1 Year Warranty Included
Availability: In stock
CAD $219.99

Description

Details

SPECIFICATIONS 
Model DescriptionPeak Energy PK12V40 rechargeable sealed lead acid (VRLA) battery
Nominal Voltage12 Volt
Capacity (@ 20hr-rate)40 Ah
Weight31.81 Lbs (14.43 kg)
Case MaterialA.B.S. (UL94-HB)
TerminalBolt and Nut Type (M6)
Maximum Short Duration Discharge Current600 Ah (5 Seconds or Less);
400 Ah (10 Seconds or Less);
240 Ah (60 Seconds or Less)
Internal Resistance6 mOhm (Fully Charged Battery) (Approx)
Energy Density (@ 20hr-rate)1.4 watt-hours/cubic inch (85.4 watt-hours/litre)
Specific Energy (@ 20hr-rate)15.09 watt-hours/pound (33.27 watt-hours/kg)
Operating Temperature RangeDischarge: -4°F (-20°C)  ~ 122°F (50°C); 
Recharge: 32°F (0°C)  ~ 104°F (40°C); 
Storage:-4°F (-20°C)  ~ 104°F (40°C)
Self Discharge RateAbout 3 %/Month @ 68 ~ 77°F (20 ~ 25°C)


DIMENSIONS

 
Length7.80 in. (198 mm)
Width6.54 in. (166 mm)
Case Height6.73 in. (171 mm)
Terminal Height6.73 in. (171 mm)

 

                               

 CHARTS

 
 
 
Constant Current Discharge Characteristics at 73.4°F (23°C)

Discharge Time

Discharge Amperes

Capacity in Ah’s

Final Voltage

Discharge

C-Rate

20.0 hr

2.0

40.00

10.50

0.05

9.2 hr

4.0

37.00

10.50

0.10

5.0 hr

6.8

33.90

10.29

0.17

4.1 hr

8

32.57

10.20

0.20

2.1 hr

14

29.80

9.94

0.35

64.0 min

24

25.60

9.54

0.6

32.5 min

40

21.64

9.00

1.0

7.2 min

120

14.36

6.00

3.0


 

Recharge Method: Connect battery to a Current Limited, Constant Voltage Source.

Limit the initial recharge current to 10 Ah or less.

To promote satisfactory performance in Cyclic applications, a minimum recharge current of 4 Ah is recommended.

Employ  Charge Voltage Temperature Compensation when battery  temperature is less than 50°F (10°C) 0r greater than 86°F (30°C), Use the Recommended voltage and normalize to 77°F (25°C).

The use of compensation through the whole temperature range is not generally necessary, but doing so may optimize service life.

If the Recommended recharge voltage is used, no Temperature Compensation is required within the range of 50 ~ 86°F (10 ~ 30°C)

Cyclic Application Recharge Voltage (77°F / 25°C)

Minimum

Recommended

Maximum

 


Volts D.C.

Per Cell

14.40

14.55

14.70

2.40

2.425

2.45

Temperature Coefficient: -2.8mV/°F/Cell (-5mV/°C/Cell)

Standby Application Recharge Voltage (77°F/25°C)

Minimum

Recommended

Maximum

 


Volts D.C.

Per Cell

13.50

13.65

13.80

2.25

2.275

2.30

Temperature Coefficient: -1.7mV/°F/Cell (-3mV/°C/Cell)