Features of the TLV12120DC - 12V 12Ah Deep Cycle Sealed Lead Acid Battery with F2 Terminals
• Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99% and freedom from electrolyte maintenance or water adding
• Not restricted for air transport-complies with IATA/ICAO Special Provision A67
• UL-recognized component
• Can be mounted in any orientation
• Computer designed lead, calcium tin alloy grid for high power density
• Long service life in float or cyclic applications
• Maintenance-free operation
• Low self discharge
Applications
• UPS Standby Power Applications
• Data Centers
• Emergency 911 Centers
• Hospitals & Medical Applications
• Military Power Equipment
• Emergency Lighting
• Fire Detection and Alarm Devices
Product Specifications
Dimensions
Terminal Type: F2
Length (mm/inch): 151/5.94
Width (mm/inch): 98/3.86
Height (mm/inch): 98/3.86
Total Height (mm/inch): 101/3.98
Approx. Weight (kg/lbs): 4.2/9.26
Performance Characteristics
Nominal Voltage: 12V
Nominal Capacity (25ºC)
12Ah@20HR-rate to 1.75V
Internal Resistance
Fully Charged battery 77ºF(25ºC): Approx. 13mΩ
Reference Capacity
C2: 8.76Ah
C3: 9.36Ah
C5: 10.3Ah
C20: 12Ah
Self-Discharge (25°C)
Battery can be stored for up to 6 months and then recharging is recommended.
Monthly self-discharge ratio is less than 3%.
Please charge battery before using. Always recharge after use.
Nominal Operating Temperature:
25°C±5°C(77°F±41°F)
Operating Temperature Range
Discharge: -20°C~60°C (-4°F~140°F)
Charge: 0°C~50°C (32°F~122°F)
Storage: -20°C~60°C (-4°F~122°F)
Float Charging Voltage (25°C):
13.7 to 13.9V Temperature compensation: -3mV/°C
Cyclic Charging Voltage (25°C):
14.6 to 14.8V Temperature compensation: -4mV/°C
Maximum Charging Current: 3.6A
Maximum Discharge Current: 180A (5 sec)
Designed Floating Life: 10 Years
Constant Current Discharge Characteristics
Constant Power Discharge Characteristics
(Note) The above characteristics data are average values obtained within three charge/discharge cycles not the mimimum values.